YORK COMMERCIAL SYSTEMS
FORM 036-21716-001 · REV. 4
Factory Technical Service Guide & Engineering Data

York Millennium Z-Series (R-410A) Packaged Rooftop Units

Comprehensive field service reference, complete 1–14 fault code diagnostic sequences, refrigerant charging metrics, electrical characteristics, and certified OEM replacement parts for York Millennium Models Z22 (25 Ton), Z23 (30 Ton), and Z24 (40 Ton).

R-410A Dual Independent Circuits 25, 30, & 40 Ton Capacities Simplicity® Elite & SEC Microprocessor 208/230V · 460V · 575V 3-Phase Constant Volume & VAV Blower

🏷️ Model Number Nomenclature Decoder

Nameplate Guide

Locate your unit model number on the data plate (located on the compressor access panel) to determine exact heating configuration, electrical voltage, and tonnage:

Z H 300 N 30 P 2 AAA1A
Z = Millennium Commercial Rooftop Series
H / F / R = Gas Heat (H) · Electric Heat (F) · Cooling Only (R)
300 / 360 / 480 = 25 Ton (300 MBH) · 30 Ton (360 MBH) · 40 Ton (480 MBH)
N = R-410A Environmentally Friendly Refrigerant
P / E / T = 460V 3-Ph (P) · 208/230V 3-Ph (E) · 575V 3-Ph (T)
2 = Second Design Generation (Millennium Z22, Z23, Z24)

⚡ Complete Diagnostic Fault Code Matrix (Simplicity® Board)

Simplicity / SEC Controls

Count the flashing green/amber LED pulses on the Simplicity control board located inside the low-voltage control cabinet. Multiple safety lockouts require manual reset:

Flash Code System Status / Condition Factory Diagnostic Root Cause Field Action / OEM Part
Steady ON Normal Operation
No faults detected
Unit is powered and running within standard factory limits. System Standby
2 Flashes Anti-Short Cycle Delay (ASCD)
Compressor delay active
Normal 5-minute timer preventing rapid compressor recycling after power dip or thermostat call. Wait 5 min timer expiration
3 Flashes High Pressure Lockout (Circuit 1)
HP1 Switch Open (>650 PSI)
Fouled condenser coils, failed outdoor fan motor 1, non-condensables, or overcharged R-410A. Order Pressure Switch →
4 Flashes High Pressure Lockout (Circuit 2)
HP2 Switch Open (>650 PSI)
Fouled condenser coils, outdoor fan motor 2 failure, or restriction in liquid line filter drier. Order Pressure Switch →
5 Flashes Low Pressure / Loss of Charge (C1)
LP1 Switch Open (<50 PSI)
Refrigerant leak, severe undercharge, failed indoor blower belt, or restricted thermal expansion valve (TXV). Order OEM TXV Valve →
6 Flashes Low Pressure / Loss of Charge (C2)
LP2 Switch Open (<50 PSI)
Circuit 2 refrigerant undercharge, stuck liquid solenoid valve, or iced evaporator coil. Order OEM TXV Valve →
7 Flashes Freezestat Trip (Evaporator)
Suction line temp <26°F
Extremely low indoor airflow, severely plugged 24x24x2 filters, or low return air temperature (<60°F). Check Blower / Filters →
9 Flashes Gas Heat High Limit / Rollout Open
Manual reset switch tripped
Heat exchanger overtemperature, cracked heat exchanger tubes, flue draft restriction, or failed inducer motor. Emergency Gas Tech →
10 Flashes Ignition Failure / Flame Loss
3 failed ignition trials
Low gas supply pressure (<5.0 in. w.g.), dirty spark igniter/flame rod, or defective 24V gas combination valve. Order Ignition Parts →
11 Flashes Air Proving Switch Open
Blower proving failure
Broken indoor blower belt, sheared motor drive pulley, loose blower wheel, or disconnected sensing tube. Order OEM Blower Belt →
13 Flashes Phase Monitor Trip
Reverse / loss phase
Utility power brownout, blown main disconnect fuse, or reversed line rotation causing reverse compressor spin. Order Phase Monitor →
14 Flashes Simplicity SEC Board Internal Fault
EEPROM / Microprocessor lock
Control transformer voltage sag (<18VAC), external electrical surge damage, or internal relay failure. Order Replacement Board →
🔧 How to Reset Hard Lockouts: A 3-strike lockout (HP1, HP2, LP1, LP2) locks the compressor off indefinitely. To clear: disconnect control power by turning off the 24V thermostat switch or pulling the 24VAC low-voltage fuse on the board for 30 seconds.

⚙️ Factory OEM In-Stock Replacement Parts

● In Stock · Overnight Freight

Verified OEM replacement components for York Millennium Z22, Z23, and Z24 packaged commercial units:

In Stock · Ready to Ship OEM Certified
Simplicity Elite Main Control Board (SEC)
OEM Part #S1-031-02630-000
Fits: York Millennium Z22, Z23, Z24 (25–40 Ton). Universal replacement for legacy IPU and SEC controllers.
In Stock · Factory Direct OEM Certified
R-410A High Pressure Cutout Switch (650 PSIG)
OEM Part #S1-025-41564-000
Auto-reset safety switch; cut-out at 650 PSIG, cut-in at 450 PSIG. Sealed 1/4" female flare connection.
In Stock · Ready to Ship OEM Certified
3-Phase Voltage & Reversing Phase Monitor
OEM Part #S1-024-35308-000
Universal 208/230V, 460V, 575V 3-Phase protection module. Prevents catastrophic reverse scroll rotation.
In Stock · Ready to Ship OEM Certified
Condenser Fan Motor (460V 3-Phase, 1.5 HP)
OEM Part #S1-024-25984-000
1140 RPM · Weatherproof ball bearing construction · Direct factory shaft length and mounting brackets.
Need Instant Schematic Verification from a Master Tech?
Standing on a roof with a confusing fault code, low superheat, or wiring trace? Chat 1-on-1 with a verified Master Commercial HVAC Technician right now ($5 trial).
Chat With Master Tech Now →

📊 Full Engineering Specifications (Z22, Z23, Z24 Models)

Form 036-21716 Data

Official mechanical and electrical design parameters for York Millennium constant volume and VAV packaged units:

Specification Parameter Z22 (25 Ton) Z23 (30 Ton) Z24 (40 Ton)
Nominal Cooling Capacity 300,000 BTU/h (25.0 Ton) 360,000 BTU/h (30.0 Ton) 480,000 BTU/h (40.0 Ton)
Refrigerant Circuits Dual Scroll (Copeland/Danfoss) Dual Scroll (Copeland/Danfoss) Tandem Scroll Staged
Factory R-410A Charge (C1 / C2) 15.0 lbs / 15.0 lbs 18.5 lbs / 18.5 lbs 24.0 lbs / 24.0 lbs
Electrical: 460V 3-Ph (MCA / MOP) 58.2 A / 70 A 69.4 A / 80 A 91.0 A / 110 A
Electrical: 208/230V 3-Ph (MCA / MOP) 124.5 A / 150 A 148.0 A / 175 A 192.5 A / 225 A
Design Airflow (CFM Range) 7,500 – 10,000 CFM 9,000 – 12,000 CFM 12,000 – 16,000 CFM
Blower Wheel Dimensions 18" x 18" Forward Curved 20" x 20" Forward Curved Dual 18" Airfoil Blower
Operating Weight (Cooling / Gas) 2,850 lbs (1,293 kg) 3,180 lbs (1,442 kg) 3,950 lbs (1,792 kg)
Cabinet Dimensions (L x W x H) 142.5" x 88.0" x 58.2" 142.5" x 88.0" x 62.5" 168.0" x 88.0" x 74.0"

❄️ Field Refrigerant Charging & Subcooling Guide (R-410A)

York Millennium systems utilize thermal expansion valves (TXV); charging must strictly be performed using the Subcooling Method, never superheat alone:

Target Subcooling Parameters at Service Port:

• Design Subcooling: 10.0°F to 14.0°F (5.5°C to 7.8°C) measured at liquid line service valve.
• Design Superheat: 12.0°F to 16.0°F (6.7°C to 8.9°C) measured at compressor suction service port.
• Required Operating Test: Ensure unit runs at 100% stage 2 cooling for at least 15 minutes before reading pressure transducers.

⚠️ Never charge R-410A as a vapor. Always invert cylinder and charge liquid slowly into suction service port using a liquid-charging manifold restrictor.

Need Commercial RTU Replacement or Mechanical Bid?

Operating an aging York Millennium Z-Series unit over 15 years old? Compare proposals from certified commercial mechanical contractors for rooftop retrofits, crane rigging, and high-efficiency rebates.

🚨 Emergency Mechanical Repair 🔄 Complete RTU Retrofit / Replacement 📋 Preventative Maintenance Agreement

📄 Wiring Sequence & Official Technical Guide (PDF)

Cooling Sequence of Operation (Stage 1 & Stage 2)

1. Call for cooling closes G (indoor blower contactor) and Y1 (cooling stage 1).

2. Simplicity board verifies high and low pressure cutouts for closed continuity.

3. 5-minute anti-recycle delay completes; Compressor 1 and Condenser Fan 1 energize.

4. Upon call for Y2, Compressor 2 and Condenser Fan 2 stage on for 100% capacity.

Economizer & Low Ambient Operating Limits

Standard mechanical cooling operates down to 35°F (1.7°C). For sub-35°F ambient operation, verify factory low-ambient head pressure damper packages and crankcase heaters.

Official York Millennium Technical Guide (PDF)
Complete 64-page electrical schematics, subcooling charts, and physical dimensions (Form 036-21716).
📥 Download PDF (4.2 MB)