Y
YORK TECHNICAL ARCHIVE
Commercial Systems & Rooftop Units
Engineering Documentation & Certified Field Support

York Millennium Z-Series (R-410A) Commercial Rooftop Units

Official technical field reference, diagnostic fault code resolution, genuine OEM replacement parts directory, and certified 24/7 commercial mechanical contractor dispatch for Models Z2 (25 Ton), Z3 (30 Ton), and Z4 (40 Ton).

R-410A High-Efficiency Refrigerant Dual Independent Scroll Circuits Simplicity® & SEC Controls 208/230V · 460V · 575V 3-Phase

⚙️ Genuine OEM Replacement Parts Directory

● Verified Inventory

Factory-certified replacement boards, sensors, and motors for York Millennium Z-Series packaged units. Available with overnight express freight:

In Stock · Ready to Ship OEM Certified
Simplicity Elite Main Control Board (SEC)
Part #S1-031-02630-000
Fits: York Millennium Z2, Z3, Z4 (25–40 Ton). Microprocessor safety circuit controller.
In Stock · Factory Direct OEM Certified
High Pressure Cutout Switch (650 PSIG)
Part #S1-025-41564-000
R-410A high-side safety auto-reset switch with factory sealed lead connectors.
In Stock · Ready to Ship OEM Certified
3-Phase Line Reversing Phase Monitor
Part #S1-024-35308-000
Compatible: 208/230V, 460V, 575V 3-Phase. Protects tandem scroll compressors against reverse rotation.
In Stock · Heavy Freight OEM Certified
Condenser Fan Motor (460V 3-Phase)
Part #S1-024-25984-000
1140 RPM · Weather-tight ball bearings · Direct factory shaft length and mounting pattern.
Need Instant Electrical Schematic or Fault Code Verification?
On-site at the rooftop with an ambiguous lock code or wiring trace? Chat 1-on-1 with a verified Master Commercial HVAC Technician right now ($5 trial).
Chat With Master Tech Now →

⚡ Diagnostic Fault Code Reference (Simplicity Board)

LED Sequence Table

York Millennium Z-Series control boards communicate operating status and safety lockouts via diagnostic LED flash sequences:

Status Code Operating Condition Diagnostic Root Cause Action / Parts
HP1 / HP2 High Pressure Lockout
Circuit > 650 PSIG
Condenser coil debris blockage, failed outdoor fan motor, or non-condensable contamination. Order Pressure Switch →
LP1 / LP2 Low Pressure Trip
Circuit < 50 PSIG
Refrigerant undercharge, TXV metering restriction, dirty filters, or evaporator freeze-up. Order TXV / Sensor →
Flash 3 Supply Fan Failure
Air proving switch open
Broken blower drive belt, sheared pulley key, or tripped VFD motor thermal overload. Order Blower Belt →
Flash 5 Board Microprocessor Lock
Internal board trip
Incoming power surge, control voltage drop (<19V AC), or failed main pilot relay. Order OEM Board →
Phase Mon Phase Monitor Red LED
Reverse / loss phase
Utility power disturbance, blown 3-phase line fuse, or reversed main input legs. Dispatch Electrician →

Need Commercial RTU Equipment Replacement or Maintenance?

Compare competitive proposals from certified commercial mechanical contractors for rooftop retrofits, crane rigging, and annual maintenance agreements.

🚨 Emergency Mechanical Repair 🔄 Complete RTU Replacement 📋 Preventative Maintenance Agreement

📊 Engineering Specifications (Z2, Z3, Z4 Models)

Factory Data Table

Factory engineering parameters for York Millennium commercial packaged cooling systems:

Tonnage & Models
Z2 (25 Ton) · Z3 (30 Ton) · Z4 (40 Ton)
Refrigerant System
R-410A (Dual Independent Circuits)
Electrical Configuration
208/230V, 460V, or 575V / 3-Phase / 60 Hz
Compressor Type
Tandem Hermetic Scroll Compressors
Design Airflow Range
7,500 – 16,000 CFM (Constant Volume or VAV)
Expansion Device
Thermal Expansion Valve (TXV) Externally Equalized

📄 Wiring Sequence & Field Installation Manuals

Cooling Sequence of Operation (Stage 1 & Stage 2)

1. Call for cooling closes G (indoor blower contactor) and Y1 (cooling stage 1).

2. Simplicity board verifies high and low pressure cutouts for closed continuity.

3. 5-minute anti-recycle delay completes; Compressor 1 and Condenser Fan 1 energize.

4. Upon call for Y2, Compressor 2 and Condenser Fan 2 stage on for 100% capacity.

Economizer & Low Ambient Operating Limits

Standard mechanical cooling operates down to 35°F (1.7°C). For sub-35°F ambient operation, verify factory low-ambient head pressure damper packages and crankcase heaters.

Official York Millennium Technical Guide (PDF)
Complete 64-page electrical schematics, subcooling charts, and physical dimensions (Form 036-21716).
📥 Download PDF (4.2 MB)